Product Overview: Phenix Technologies PATTR-03 3 Phase Transformer Turns Ratio Test Set
Phenix Technologies PATTR-03 Features:
- Microprocessor-based
- Automatic
- Single and 3 Phase
- Portable
- Lightweight
- Rugged
- Self-Calibrates before each measurement
- Also measures excitation current and phase angle
- 20 charachter x 4 line back-lighted LCD display
- Results can be printed immediately on a built in 4.5 inch thermal printer
- Store up to 200 transformer test records in Flash EEPROM, reach record may contain up to 99 ratio, excitation current, phase angle, and nameplate voltage readings
- Downloadable to PC (Windows based software package included
- Able to create a test plan for a specific transformer
Phenix Technologies PATTR-03 Specs:
- Dimensions: 17”Lx13”Wx7”H
- Weight: 14 lbs
- Power: 120/240 VAC, 50/60 Hz
- Ratio-Measuring Ranges: 0.8 to 15,000
- Turns-Ratio Accuracy:
- 0.8-1999 +/- 0.1%, 2000-3999 +/- 0.25%, 4000-15,000 +/- 1% @ 8 VAC
- 0.8-1999 +/- 0.1%, 2000-3999 +/- 0.20%, 4000-15,000 +/- 1% @ 40 VAC
- 0.8-1999 +/- 0.1%, 2000-3999 +/- 0.15%, 4000-15,000 +/- 1% @ 100 VAC
- Calibration: None required
- Excitation Voltage: 8VAC, 40VAC, 100VAC
- Current Accuracy:+/- 2% of reading (+/- 1 digit)
- Phase Angle Measurement: 0-360 Degrees
- Phase Angle Accuracy: +/- 0.2 Degree (+/- 1 digit)
- Computer Interface: RS-232C, 19,2000 baud
- PC Software: Windows-based, included
- Test Storage: 200 complete transformer test records. Each test record includes nameplate voltage, winding turns ratio, excitation current, and winding phase angle. Data can be retained for 2 years
- Temperature:
- Operating: -10°C to 50°C (15°F to +122°F)
- Storage: -30°C to 70°C (-22°F to +158°F)
- Cables:
- One 15 ft (5m) single-phase cable set
- One 15 ft (5m) three-phase cable set
- One 30 ft (10m) extension cable set
- One input power cord
- One ground lead
- One cable-carrying bag included
NOW OFFERING DAILY RENTAL RATES ON THIS ITEM! CALL TODAY!
See more TTR Testers here.
Reviews
There are no reviews yet.