TEST EQUIPMENT
MADE EASY ™

Raytech TR-Mark III Three Phase Turns Ratiometer

Raytech TR-MARK III Three Phase Turns Ratiometer

View Quote List
QTY:
 
Manufacturer

RENT THIS ITEM

Daily, Weekly, and Monthly rates are available on select items.

CALIBRATION SERVICES

Calibration, inspection, cleaning, and/or repair may be available for this item.

Product Overview: Raytech TR-Mark III Three Phase Turns Ratiometer

Raytech TR-Mark III: Fully Automatic, Three Phase Transformer Turns Ratio Meter

The Raytech TR-Mark II system is made to be simple to use and comprehend. The system is relatively easy to comprehend and use after the buttons and few choices are grasped. This clever technology examines a transformer’s setup and automatically takes all necessary measurements for Voltage Ratio, Turns Ratio, Current, and Phase Displacement. With just one click of a button, the system can complete a three-phase testing procedure. To test, connect the leads, choose the transformer configuration, and press GO.

The TR-Mark III 250V is a high accuracy, completely automatic, microprocessor-based device for testing the turns ratio of single and three phase transformers. This technology is made to provide on-site, laboratory-quality readings that are extremely accurate. It is the most precise system on the market.

This newly created measurement method includes a rectification resolution circuit for phase displacement and a high precision dual-vector voltage meter for ratio readings (vector group). Without the need for human interaction, the phase displacement (vector group) can be automatically recognized and shown.

The TR-Mark III 250V applies a tiny voltage to the transformer’s HIGH winding side and then measures the result through the transformer’s LOW side. The system makes an analysis and decides if a test can go ahead. The system then applies the test voltage to the transformer’s HIGH winding side and monitors the voltage that returns through the transformer’s LOW side. The safest form of ratio testing has been found to be this approach. On the simple to read touch-screen display, the results are shown.

The system starts up by performing a self-calibrating and circuit checking routine. The operator is informed right away if any issues are found either during this initialization phase or while the system is in use. The condition of the transformer being tested is continuously monitored by the system. Even shorted leads can be detected by the TR-Mark III 250V, which will then end the test without causing any harm to the test tools. This is particularly effective when test leads unintentionally come loose from the transformer during full voltage measurement. The measurement is safely stopped when the test leads on the High and Low voltage side are accidentally switched.

The TR-Mark III requires no maintenance due to the utilization of high accuracy components of the design.

Key Features

  • Automatic measurements of voltage, turns ratio, current, and phase displacement
  • Easy one time hook up to the transformer
  • Automatic test voltage range
  • Displays deviation from a nominal ratio
  • Simple touch screen operation
  • Graphical tap changer display
  • Tap changer interface
  • Load on test object <0.05 VA
  • Measures power transformers PTs & CTs
  • Displays % error vs. name plate value
  • Automatic phase vector detection
  • Enhanced heavy-duty protection circuitry
  • Emergency stop push button immediately turns off output
  • Internal printer
  • Data storage of over 10,000 measurements
  • Data exchange with USB-key
  • Mounted in rugged case for field-testing
  • 5 Year standard warranty*

Equipment/Cable Set/Accessories:

  • Raytech TR-Mark III instrument
  • Cable Bag
  • H and X Lead Set – 5m (16ft), 4.1cm (1.6in) jaw opening
  • Red Extension Lead Set (2) – 10m (32ft)
  • Power Cord – 6.09m (20ft)
  • Ground Lead – 5m (16ft)
  • A-B USB Cable – 3.05m (10ft)
  • RS-232 Cable – 3.05 (10ft)
  • External USB drive
  • Instruction Manual
  • Paper Refill for Panel-mount Printer – 5 rolls
  • Stylus
  • External Zippered Pouch
  • Cable Bag with Shoulder Strap
  • Certificate of Accuracy

Accuracy

Range Accuracy at 100V or 40V Accuracy 10V Resolution
0.8 – 2,000 ±0.06% Rdg ±1 LSD ±0.15% Rdg ±2 LSD 5 digits
2,001 – 4,000 ±0.1% Rdg ±1 LSD ±0.22% Rdg ±2 LSD 5 digits
4,001 – 13,000 ±0.3% Rdg ±1 LSD ±0.5% Rdg ±2LSD 5 digits
13,000 – 16,000 ± 0.4% Rdg ±1 LSD not specified 5 digits

 

Current Accuracy Resolution
0 – 1A ±0.001 A 0.1 mA

 

Phase Angle Accuracy Resolution
±90 Degree ±0.05 Degree 0.01 Degree

 

Specifications

  • Model: TR-MARK III
  • Size: L: 470mm (18.5″) W: 371mm (14.6″) H: 190mm (7.5″)
  • Weight: 9.5kg (21 lbs)
  • Input Line Power: 100 to 250 VAC 47-63 Hz, auto ranging, Fuse: 2A
  • Test Voltage: User selectable 100, 40, 10, and 1 VAC, 1A
  • Panel Display: Color LCD with back lighting and touch screen
  • Front Panel: Sealed anodized
  • Interface: 9 pin RS 232 serial / 2 USB 1.1 (1 host, 1 device)
  • Memory Storage: Stores over 1,000 complete test results
  • Ratio Range: 0.1 – 16,000
  • Operating Temperature: -10ºC to 60ºC (14ºF to 140ºF)
  • Storage Temperature: -20ºC to 70ºC (-4ºF to 158ºF)

Reviews

There are no reviews yet.

Be the first to review “Raytech TR-Mark III Three Phase Turns Ratiometer”

Your email address will not be published. Required fields are marked *


Rent the Raytech TR-Mark III Three Phase Turns Ratiometer

Request Rental Quote Above

JM Test Rental options can help you save capital, get the latest technology, and expand your capabilities. Daily, Weekly and Monthly rates are available on select items.

Raytech TR-Mark III Three Phase Turns Ratiometer Calibration

Request a Calibration Quote

Calibration, inspection, cleaning, and/or repair may be available for the Raytech TR-Mark III Three Phase Turns Ratiometer. Click to inquire about our calibration or other services.